Install the Four-Post Rack Kit on a PA-5200 Series Firewall
Expand all | Collapse all
Install the Four-Post Rack Kit on a PA-5200 Series Firewall
Learn how to install the optional four-post rack kit.
The following procedure describes how to install
the optional four-post rack kit (PAN-PA-5200-RACK4) to provide additional
support to the back of the firewall. This kit supports rack depths from
23 to 32 inches (measured between the inner-parts of the vertical
rails).
Attach one rack-mount bracket to each side of
the firewall in the front-mount position using nine #8-32 x 5/16”
screws for each bracket and torque to 15 in-lbs.
Attach one rack-mount rail to each side of the firewall
using four #8-32 x 5/16” screws for each bracket and torque to 15
in-lbs. The side brackets are universal but you must install them
with the beveled edge facing the firewall.
With help from two other people, hold the firewall in
the rack and secure the rack-mount brackets to the front rack posts
using four screws for each bracket. Use the appropriate screws (#10-32 x
3/4” or #12-24 x 1/2”) for your rack and torque to 25 in-lbs. Use
cage nuts (not provided) to secure the screws if the rack has square
holes.
Slide one back rack-mount bracket onto each of the two
previously installed side rack-mount rails and secure the brackets
to the back rack posts using four screws for each bracket (#10-32
x 3/4” or #12-24 x 1/2”) and torque to 25 in-lbs. Use cage nuts
(not provided) to secure the screws if the rack has square holes.