Install the Four-Post Rack Kit on a PA-5200 Series Firewall

Table of Contents

Install the Four-Post Rack Kit on a PA-5200 Series Firewall

Learn how to install the optional four-post rack kit.
The following procedure describes how to install the optional four-post rack kit (PAN-PA-5200-RACK4) to provide additional support to the back of the firewall. This kit supports rack depths from 23 to 32 inches (measured between the inner-parts of the vertical rails).
  1. Attach one rack-mount bracket to each side of the firewall in the front-mount position using nine #8-32 x 5/16” screws for each bracket and torque to 15 in-lbs.
  2. Attach one rack-mount rail to each side of the firewall using four #8-32 x 5/16” screws for each bracket and torque to 15 in-lbs. The side brackets are universal but you must install them with the beveled edge facing the firewall.
  3. With help from two other people, hold the firewall in the rack and secure the rack-mount brackets to the front rack posts using four screws for each bracket. Use the appropriate screws (#10-32 x 3/4” or #12-24 x 1/2”) for your rack and torque to 25 in-lbs. Use cage nuts (not provided) to secure the screws if the rack has square holes.
  4. Slide one back rack-mount bracket onto each of the two previously installed side rack-mount rails and secure the brackets to the back rack posts using four screws for each bracket (#10-32 x 3/4” or #12-24 x 1/2”) and torque to 25 in-lbs. Use cage nuts (not provided) to secure the screws if the rack has square holes.